Test & Measurements
-
MULTIFUNCTON INSTALLATION TESTER - Bluetooth Version ( Kyoritsu )
Product code:
KEW6516BT
Description:Insulation resistance SPD(Varistor)
• Test voltage:100V 250V 500V 1000V Max.1000V
• Measuring ranges: 2.000/20.00/200.0M/1000M/2000M (Auto-ranging)
• Accuracy: ±2%rdg±6dgt...±5%rdg±6dg
• Rated current: 1.0-1.2mA
• Short circuit current: 1.5mA max
Loop impedance
• Function: LOOP ATT LOOP HIGH
L-PE/L-N(3wire) L-PE(2wire) L-PE(0.01Res) L-PE(0.001Res) L-N/L-L
• Rated voltage 100-260V(50/60Hz),48-260V(50/60Hz),100-260V(50/60Hz),48-500V(50/60Hz)
• Impedance range: 2.000/20.00/200.0/2000(Auto-ranging)
• Accuracy:±3%rdg±6dgt
• Nominal test current at 0 external loop: L-N:6A/60ms; N-PE:10mA; L-PE:15mA 20:6A/20ms; 200:0.5A/20ms; 2000:15mA/500ms; 25A/20ms 6A/20ms
PSC/PFC
• Range 2000A/20kA(L-N(PSC)/L-PE(PFC)),2000A/20kA(PFC,PSC),2000A/50kA(PFC)
• Accuracy:PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification
RCD
• Rated voltage 100-260V(50/60Hz)
• Function: x1/2, x1,x5,Ramp,Auto,Uc; 6/10/30/100/300/500/1000mA/variable
• RCD type:AC(G/S) A(G/S) F(G/S) B(G/S)
• Trip current setting: x1/2,x1,Uc 10/30/100/300/500/1000mA(G),
• Ramp: 10/30/100/300/500mA 10/30/100/300/500mA 10/30/100/300/500mA 10/30/100/300mA
• Accuracy Trip current: -8% - -2% ; -10% - 0%; 0% - +10% ; Ramp -4% - +4%, -10% - +10%
• Trip time: x1/2 2000ms(G/S):±1%rdg±2ms ; x1 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms; x5 410ms(G/S):±1%rdg±2ms
Continuity
• Range: 20.00/200.0/2000 (Auto-ranging);
• Open circuit voltage: (DC) 7-14V ;
• Measuring current: 200mA >200mA or more(2 or less); 15mA 15mA±3mA(short-circuit)
• Accuracy: ±2%rdg±8dgt
Volts
• Range 300.0/600V(Auto-ranging);
• Measuring ranges: Volts 2-600V (Accuracy: ±2%rdg±4dgt)
• Frequency 45-65Hz ( accuracy: ±0.5%rdg±2dgt )
Phase Rotation,
• Rated voltage: 48-600V(50/60Hz);
• Remarks Remarks Correct phase sequence: are displayed "1.2.3" and mark Reversed phase sequence: are displayed "3.2.1" and mark
Earth
• Range: 20.00/200.0/2000(Auto-ranging)
• Accuracy: ±2%rdg±0.08(20.00), ±2%rdg±3dgt(200.0/2000)
General
• Applicable Standards: IEC 61010-1 CAT Ⅳ 300V,CAT Ⅲ 600V Pollution degree 2, IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10, IEC 60529(IP40), IEC 61326(EMC)
• Communication Interface: USB , AndroidTM 5.0 or more, iOS 10.0 or more; Bluetooth
• Power source: LR6(AA)(1.5V) × 8
• Dimensions: 136(L) × 235(W) × 114(D)mm
• Weight: 1300g
• Included Accessories: Main test lead*², 7281(Test leads with remote control switch), 7246(Distribution board test lead), 7228A(Earth resistance test leads), 8041(Auxiliary earth spikes[2 spikes/1 set])
9084(Soft case), 9142(Carrying case), 9151(Shoulder strap), 9199(Shoulder pad), LR6(AA) × 8, Instruction manual, Calibration certificateYesPrice (VAT included):
1286.09 €