CATALOG PRODUCTS
-
Industrial DIN Rail Power Supply - Single Output - 32.5 W - 5 V - 6.5 A
Product code:
HDR-60-5
Description:
Features:- ultra slim design with 52.5 mm (3SU) width
- universal input 85-264 VAC (277 VAC operational)
- no load power consumption < 0.3 W
- isolation class II
- pass LPS (limited power source)
- DC output voltage adjustable
- protections: short circuit / overload / over voltage
- cooling by free air convection (working temperature : -30 - +70°C)
- DIN rail TS-35/7.5 or 15 mountable
- over voltage category III
- LED indicator power on
- 3 year warranty
- for professional use only
- This device must be installed by a qualified person.
- output:
- DC voltage: 5 V
- rated current: 6.5 A
- current range: 0 - 6.5 A
- rated power: 32.5 W
- ripple & noise (max.): 80 mVp-p
- voltage adj. range: 5.0 - 5.5 V
- voltage tolerance: ± 2.0 %
- line regulation: ± 1.0 %
- load regulation: ± 1.0 %
- setup, rise time: 500 ms, 50 ms / 230 VAC - 500 ms, 50 ms / 115 VAC at full load
- hold up time (typ.): 30 ms / 230 VAC - 12 ms / 115 VAC at full load
- input:
- voltage range: 85-264 VAC (277 VAC operational) - 120-370 VDC (390 VDC operational)
- frequency range: 47 - 63 Hz
- efficiency (typ.): 85 %
- ac current (typ.): 1.2 A / 115 VAC - 0.8 A / 230 VAC
- inrush current (typ.): cold start 30 A / 115 VAC - 60 A / 230 VAC
- protection:
- overload:
- 105 - 160 % rated output power
- protection type: constant current limiting, recovers automatically after fault condition is removed
- overvoltage:
- 5.75 - 6.75 V
- protection type: shut down output voltage, re-power on to recover
- environment:
- working temperature: -30 to +70 °C
- working humidity: 20 to 90 % RH non-condensing
- storage: -40 to +85 °C, 10 to 95% RH
- temperature coefficient: ± 0.03 %/°C (0 - 50°C )
- vibration: 10 - 500 Hz, 2G 10 min / 1 cycle, 60 min each along X, Y, Z axes; mounting: compliance to IEC60068-2-6
- operating altitude: 2000 m
- over voltage category: III, according to EN61558, EN50178, EN60664-1, EN62477-1, altitude up to 2000 meters
- safety & EMC:
- safety standards: UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved, design refer to TUV EN60950-1
- withstand voltage: input to output: 4 kVAC
- isolation resistance: input to output: 100 MOhm / 500 VDC / 25 °C / 70 % RH
- EMC emission:
- conducted (EMC emission): EN55032 (CISPR32) / Class B
- radiated: EN55032 (CISPR32) / Class B
- harmonic current: EN61000-3-2 / Class A
- voltage flicker: EN61000-3-3
- EMC immunity:
- ESD: EN61000-4-2 / Level 3, 8KV air - Level 2, 4KV contact - criteria A
- radiated susceptibility: EN61000-4-3 / Level 3 - criteria A
- EFT/Burest: EN61000-4-4 / Level 3 - criteria A
- surge: EN61000-4-5 / Level 4, 2KV/L-N - criteria A
- conducted (EMC immunity): EN61000-4-6 / Level 3 - criteria A
- magnetic field: EN61000-4-8 / Level 4, criteria A
- voltage dips and interruptions: EN61000-4-11 / >95% dip 0.5 periods, 30% dip 25 periods - >95% interruptions 250 periods
- other:
- MTBF: 927.6Kh, MIL-HDBK-217F (25 °C)
- dimensions: 52.5 x 90 x 54.5 mm (W x H x D)
- overload:
Documents:On orderPrice (VAT included):
43.74 €